MICRO INPUT MODULE
- MICRO INPUT MODULE
PAD100-MIM Micro Input Module
The Potter PAD100-MIM is a compact addressable micro input module designed to monitor initiating devices containing normally open dry contacts. It is compatible with Potter addressable fire alarm systems using the PAD Addressable Protocol.
- One Class B contact monitoring input
- Compact micro-module design
- SLC Class A, Class X & Class B
- 6-inch pigtail wiring connections
- Red LED status indication
- Compatible with Potter IPA and AFC/ARC series panels
- 5-year product warranty
- UUKL Listed for Smoke Control
Product Overview
The PAD100-MIM is a micro input module used to monitor the status of initiating devices that contain normally open dry contacts. The module is enclosed in a protective plastic case and can be mounted using a single screw.
The module includes a status indicator LED for communication and alarm conditions. During normal operation the LED flashes when the device is being polled by the control panel. When the input is activated, the LED flashes at a faster rate.
Typical Applications
- Pull station monitoring
- Normally open dry-contact devices
- Initiating device monitoring
- Addressable fire alarm systems
- Installation inside electrical boxes
- Installation behind monitored devices
Technical Specifications
| Product | |
|---|---|
| Model | PAD100-MIM |
| Product Type | Micro Input Module |
| Manufacturer | Potter Electric Signal Company, LLC |
| Input | One Class B Contact Monitoring Input |
| Protocol | Potter PAD Addressable Protocol |
| Electrical | |
| Operating Voltage | 24.0 VDC |
| Max SLC Standby Current | 200 µA |
| Max SLC Alarm Current | 200 µA |
| IDC Input Circuit | Class B |
| Max IDC Wiring Resistance | 100 Ω |
| Max IDC Wiring Capacitance | 1 µF |
| Max IDC Voltage | 2.05 VDC |
| Max IDC Current | 120 µA |
| EOL Resistor | 5.1 kΩ |
| Environmental | |
| Operating Temperature | 32°F to 120°F (0°C to 49°C) |
| Operating Humidity | 0–93% Non-Condensing |
| Mechanical | |
| Dimensions | 1.75 × 1.36 × 0.43 in |
| Mounting | 2-1/2 in Deep Single-Gang Box |
| Maximum Modules per Loop | 127 Units |
| Shipping Weight | 0.3 lbs |
| Wiring Connections | 6-inch Pigtail Connections |
Specifications should be verified against the latest manufacturer documentation and the requirements of the compatible fire alarm control panel before installation.
Key Features
Micro Design
The compact enclosure allows installation in most electrical boxes and behind monitored devices.
Class B Input
Provides one Class B contact monitoring input for compatible initiating devices.
Addressable Operation
Designed for Potter addressable fire alarm systems using the PAD Addressable Protocol.
LED Status
The red LED indicates communication with the control panel and input activation status.
Flexible Mounting
Designed for installation in a 2-1/2-inch deep single-gang box or suitable enclosure.
Dry Contact Monitoring
Suitable for monitoring initiating devices containing normally open dry contacts.
Product Documents
Access the Product Data Sheet, Quick Start Guide and User Manual for the Potter PAD100-MIM Micro Input Module.
Need this for a project?
Send us your BOQ or project requirements and we'll prepare a quote.